Guide

Fan Blade Selection Guide

The six key parameters for choosing a Multi-Wing fan blade, how to read the product code, and a material comparison.

How to read a Multi-Wing product code

The label of a Multi-Wing impeller usually carries a code similar to the one below. Writing the full code in the note field of your quote list is the fastest way for us to identify the right product.

800Diameter (mm)/8Blades-8Hub sockets/45Pitch (°)/PAGMaterial/7ZLProfile + hand/38Bore (mm)/10Keyway (mm)/82Hub/AMounting side

1. Diameter

The fan diameter follows the inner diameter of the shroud or venturi ring. The smaller the gap between blade tip and shroud (tip clearance), the higher the efficiency and the lower the noise. Since Multi-Wing profiles can be cut in 1 mm steps, a diameter that fits your shroud exactly can be produced.

2. Number of blades

More blades give more pressure capacity at the same diameter and speed. Modular hubs allow different blade counts; just tell us how many blades your current impeller has.

3. Profile

Airfoil profiles (e.g. 4Z, 6W) give high efficiency, sickle profiles (e.g. 1Z, 2W) low noise, PMAX profiles high pressure, reversible TR profiles reverse flow, and broad paddle profiles strong thrust at low speed.

4. Pitch angle

A higher pitch moves more air but draws more power from the motor. The right pitch depends on motor power and target duty point; never increase it arbitrarily, or the motor may be overloaded.

5. Rotation

Viewed from the air outlet side, impellers turning clockwise are right-hand (R) and those turning anticlockwise are left-hand (L). The L or R at the end of the profile code (e.g. 4ZL, 6WR) shows the rotation.

6. Material

Material is chosen by operating temperature, humidity, chemical exposure and flammability requirements. The table below compares Multi-Wing materials.

Material comparison

CodeMaterialTemperature rangeKey feature
PPGGlass reinforced polypropylene−30 / +90 °CLightweight and durable; general HVAC and ventilation.
PAGGlass reinforced polyamide−60 / +120 °CHigh strength and vibration resistance.
PAGV1Low-flammability polyamide−60 / +120 °CRail and other low-flammability applications.
PAGASAnti-static glass reinforced polyamide−60 / +120 °CPotentially explosive atmospheres (ATEX).
PAG6-CCarbon fibre reinforced polyamide−60 / +120 °CExtreme operating conditions, anti-static.
ALAluminium−60 / +245 °CHigh-temperature drying applications.
AL 400CAluminium (400 °C)400 °C / 2 saat testTunnel ventilation and smoke extraction.

Let’s pick the right blade together

Send us a photo and the dimensions of your blade and we will quickly come back with the matching product and price.

Added to your quote list
View list